K5942V2 7/04
5894PI
PASSIVE INFRARED MOTION DETECTOR/TRANSMITTER
INSTALLATION INSTRUCTIONS
GENERAL INFORMATION
The 5894PI Passive Infrared
Detector/Transmitter is 10-year battery-
operated wireless device intended for use as
part of a 5800 series wireless alarm system.
SPECIFICATIONS
Pet Immune Lens:
35 ft x 45 ft (10.6m x 13.7m).
28 zones (8 over, 8 long range, 8 intermediate,
4 short-range).
BATTERY ACTIVATION/INSTALLATION
Motion
1. Remove front cover by pressing the front
cover latch and lifting the cover off. See
Figure 2.
a
Designed for use in commercial and residential
installations, the 5894PI is a wall-mounted unit
with a standard lens that provides wide-angle
protection up to a range of 35 ft (10.6m). For
best coverage, mount the detector so that the
likely direction of intruder motion is across the
pattern.
When installed per the guidelines, the Tier-
Balanced Optics technology in the 5894PI
provides false alarm protection against pets
and other animals up to 80 lbs.
This document provides installation instructions
for the 5894PI, but the installer must be familiar
with the installation instructions for the 5800
Wireless Alarm System with which the 5894PI
is intended to be used.
Pulse Processing:
Intermediate, Standard, or Harsh, Installer-
selectable. Note: For pet immune applica-
tions, see Special Instructions for
Installations with Pets on page 3.
Detectable Walk Rate:
0.5–10 ft/Sec (0.15–3m/Sec).
Mounting Height:
7.0 ft (2.1m)
Walk Test Indicator:
Red LED with enable/disable link.
Batteries:
Three 3-volt Lithium batteries. Use only
ADEMCO No. 466, Duracell DL123A,
Panasonic CR123A, Sanyo CR123A, or Varta
CR123A.
0perating Temperature:
32°F – 122°F (0°C - 50°C).
FEATURES
• Tier-Balanced Optics provides pet immunity
against animals up to 80 lbs.
Operating Humidity:
Up to 95% RH (max.), non-condensing.
• Wireless operation for fast installation.
Dimensions:
3.0"W 5.0"H x 1.7"D
(76.3mm x 127.0mm x 42.6mm).
• Dual-element pyroelectric sensor provides
positive protection while minimizing false
alarms.
• Selectable PIR sensitivity.
• Provision to turn LED on while Walk Testing
(LED is turned off after testing).
Figure 2. Remove the Front Cover
Approvals/Listings:
FCC, IC, cULus, C-Tick
2. To activate the installed batteries, remove
the battery pull-tab. (See Figure 3.) Make
sure the batteries remain firmly seated in
the battery holders.
TOP VIEW
22.5'
•
Tamper-protected cover and wall; detector
transmits message if cover or detector is
removed.
•
•
•
Wall or corner mounting options.
Patented Black Bug Guard.
Temperature compensation.
SYSTEM DESCRIPTION
Optical System
0
The 5894PI uses efficiently designed Fresnel
lenses with Tier-Balanced Optics.
Radio Transmitter
.
The built-in transmitter serves only as the
communication link to the alarm system's
Receiver/Control, and can send alarm, tamper,
supervisory, and battery status messages to
the system's receiver/control. The transmitter is
not used for detection purposes. Each detector
has a unique ID code permanently assigned at
the factory. You must enroll this ID into the
control system at the time of installation. This
allows each detector used in the system to be
uniquely identified. You must program the
control to enroll the 5894PI as an "RF" type unit
(i.e., supervised RF).
Figure 3. Remove Pull Tab to
activate batteries
22.5'
10'
20'
30' 35'
3. To replace the batteries, remove the old
batteries from the holder. Then, observing
correct polarity, install three new Lithium
batteries into the battery holders, as shown
in Figure 4. Make sure the batteries are
firmly seated.
ALTERNATE
COUNT POLARITY
EACH ZONE CONSISTS
OF 2 FIELDS
4. Replace the cover (snap fit).
SIDE VIEW
Battery Caution
To conserve battery life during normal
operation, no more than one transmission
sequence will occur within a 3-minute period.
There is no such time restriction in Test mode
(refer to the Walk Test section).
7'
0
Risk of fire, explosion, and burns. Do not
recharge, disassemble, heat above 100°C, or
incinerate. Dispose of used batteries promptly.
Keep away from children.
10'
20'
30' 35'
0
Figure 1. Protection Pattern
Page 1
Note: Each time you remove and replace the
front cover, or remove and replace the sensor
in the mounting plate, the sensor will transmit
every alarm signal for 64 alarm events.
1. Remove front cover, and set the pulse
count jumper as required in the installation
(INT, STD or HARSH),
2. Enable the LED by placing the jumper link
in the TEST position (see Figure 4 for
jumper location).
TEST PROCEDURES
MAINTAINING PROPER OPERATION
In order to maintain the detector in proper
working condition, it is important that the user
observes the following:
Important: Testing should be conducted with
the protected area cleared of all people. Place
the protective system's control in the Test
mode for the Walk Test procedure. When the
PIR senses movement, the system's console
1. Replace all three batteries within seven (7)
days after a "low battery" message has
appeared in the system's display.
2. Detectors should never be re-aimed or
relocated without the advice or assistance
of the alarm service company.
3. The physical surroundings of the protected
area should not be changed. If furniture or
stock is moved, or air conditioning or
additional heating is installed, the PIR may
have to be readjusted.
4. Walk Tests should be conducted frequently
(at least weekly) to confirm continued
proper coverage.
emits
a
beep, verifying that the PIR's
transmitter signal has reached the control's
wireless receiver.
The absolute range of all PIR units is subject to
variation because of different types of clothing,
backgrounds, and ambient temperature. For
this reason, ensure that the most likely intruder
routes are well within the PIR's protective
zones and that Walk Testing is carried out
along these routes.
Note:
Removing the front cover, or
removing the sensor from the mounting
plate, will also enable the LED.
3. Replace front cover and walk through
protective zones, observing that the
detector's LED lights whenever motion is
detected (the LED serves as a Walk Test
indicator during this procedure).
WALK TEST
Test mode is initiated by removing and
replacing the detector’s front cover, or by
removing and replacing the sensor from the
mounting plate.
4. After the Walk Test is completed, disable
the LED by placing the LED jumper link
in the Normal position. Failing to do so
will reduce the battery life. (see Figure 4.)
SPECIAL INSTRUCTIONS FOR INSTALLATION WITH PETS
To take full advantage of the pet immunity in the 5894PI, the guidelines below should be followed:
•
•
•
Mount the center of the detector 7.0 feet high.
Set the Pulse Count to Standard or Harsh.
Mount where animals/rodents cannot come within six feet of the detector by climbing on
furniture, boxes, or other objects.
•
Do not aim the detector at stairways or furniture / objects that can be climbed by an animal.
Note: This unit will provide immunity to false alarms for an individual animal or a group of animals
whose total weight is equal to or less than 80 pounds when the room temperature is above 50° F.
TROUBLESHOOTING
Trouble 1: INTERMITTENT ALARM
Trouble 4: SUPERVISION FAILURE
Probable Causes:
Probable Causes:
A. Rapid temperature change. Check for electric or gas heaters,
open flames, electric arcs, etc.
A. When enrolling the detector, a tamper signal was used to transmit
the detector serial number, and the panel enrolled the detector with a
loop type “4”, or the wrong device was learned.
Remedy: Locate source and re-position detector.
B. Drafts causing drapes, light fixtures, display material to move.
Remedy: Eliminate source of motion.
Remedy: Ensure the serial number and loop types are correct for
each detector; if the detector loop type is programmed as “4”,
manually change it to “1” at the panel. If the wrong device was
learned, enroll the detector again (see Programming on page 2).
Trouble 2: LED INOPERATIVE DURING WALK TEST
Probable Causes:
B. The detector was placed in a location where the RF signal is not
strong enough.
A. LED control jumper set to NORMAL position.
Remedy: Re-position jumper to TEST position (see Figure 4).
B. LED malfunction. Check for broken/shorted leads.
Remedy: Return unit for service.
Remedy: Repeat the directions to verify the transmission path (see
the Radio Transmission Path Check section on page 2). If
necessary, move the detector to a new location.
Trouble 5: UNIT DOES NOT APPEAR TO BE OPERATING
Probable Cause:
A. Unit is not receiving power.
Trouble 3: LED OPERATIVE WITH LED JUMPER LINK SET
TO NORMAL (OFF) POSITION
Remedy: Check for appropriate battery voltage. Install new batteries
if necessary. Be sure to change all batteries.
Probable Causes:
A. The sensor is not mounted squarely on the wall, (the wall
tamper switch is not depressed.)
Trouble 6: UNIT IS ALWAYS IN TEST MODE
Probable Cause:
Remedy: Re-position the sensor to make sure the wall
tamper switch is fully depressed.
B. The sensor’s front cover is not installed.
Remedy: Replace the sensor’s front cover.
A. The sensor front cover was removed and replaced, or the sensor
was removed and replace in the mounting plate, so the sensor is
transmitting every alarm signal for 64 alarm events.
Remedy: Wait for the sensor to transmit 64 alarm events.
Page 3
LIMITATIONS OF THE PIR MOTION DETECTOR
LIMITED WARRANTY
While the Intrusion Detector is a highly reliable intrusion detection
device, it does not offer guaranteed protection against burglary. Any
Intrusion Detection device is subject to compromise or failure to warn
for a variety of reasons:
Honeywell International Inc. (“Seller”), 165 Eileen Way, Syosset, New
York 11791, warrants its product(s) to be in conformance with its own
plans and specifications and to be free from defects in materials and
workmanship under normal use and service for 24 months from the
date stamp control on the product(s) or, for product(s) not having an
Honeywell date stamp, for 12 months from date of original purchase
unless the installation instructions or catalog sets forth a shorter
period, in which case the shorter period shall apply. Seller's obligation
shall be limited to repairing or replacing, at its option, free of charge for
materials or labor, any product(s) which is proved not in compliance
with Seller's specifications or proves defective in materials or
workmanship under normal use and service. Seller shall have no
obligation under this Limited Warranty or otherwise if the product(s) is
altered or improperly repaired or serviced by anyone other than
Honeywell factory service. For warranty service, return product(s)
transportation prepaid, to Honeywell Factory Service, 165 Eileen Way,
Syosset, New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF
MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE
OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION
ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE
TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL
DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY,
EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF
LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS
CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
• Passive Infrared Motion Detectors can detect intrusion only within the
designed ranges as diagrammed in this installation manual.
• Passive Infrared Motion Detectors do not provide volumetric area
protection. They do create multiple beams of protection, and intrusion
can be detected only in unobstructed areas covered by those beams.
• Passive Infrared Detectors cannot detect motion or intrusion that
takes place behind walls, ceilings, floors, closed doors, glass
partitions, glass doors, or windows.
• Mechanical tampering, masking, painting, or spraying of any material
on the lenses, windows or any part of the optical system can reduce
the detection ability of the Passive Infrared Motion Detector.
• Passive Infrared Detectors sense changes in temperature; however,
as the ambient temperature of the protected area approaches the
temperature range of 90° to 105°F (32° to 40°C), the detection
performance can decrease.
• This Passive Infrared Detector will not operate without the
appropriate battery installed, or if the battery is weak or improperly
connected (i.e., reversed polarity).
• Passive Infrared Detectors, like other electrical devices, are subject
to component failure. Even though this equipment is designed to last
as long as 10 years, the electronic components in it could fail at any
time.
We have cited some of the most common reasons that a Passive
Infrared Motion Detector can fail to catch intrusion. However, this does
not imply that these are the only reasons, and therefore it is
recommended that weekly testing of this type of unit, in conjunction with
weekly testing of the entire alarm system, be performed to ensure that
the detectors are working properly.
Installing an alarm system may make the owner eligible for a lower
insurance rate, but an alarm system is not a substitute for insurance.
Homeowners, property owners and renters should continue to act
prudently in protecting themselves and continue to insure their lives and
property.
We continue to develop new and improved protection devices. Users of
alarm systems owe it to themselves and their loved ones to learn about
these developments.
Seller does not represent that the product(s) it sells may not be
compromised or circumvented; that the product(s) will prevent any
personal injury or property loss by burglary, robbery, fire or otherwise;
or that the product(s) will in all cases provide adequate warning or
protection. Customer understands that
a
properly installed and
maintained alarm system may only reduce the risk of a burglary,
robbery, fire, or other events occurring without providing an alarm, but
it is not insurance or a guarantee that such will not occur or that there
will be no personal injury or property loss as
a
result.
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY
PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS
BASED ON A CLAIM THAT THE PRODUCT(S) FAILED TO GIVE
WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER
DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE
ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE,
REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM
LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE
PRICE OF THE PRODUCT(S), WHICH SHALL BE THE COMPLETE
AND EXCLUSIVE REMEDY AGAINST SELLER.
This warranty replaces any previous warranties and is the only
warranty made by Seller on this product(s). No increase or alteration,
written or verbal, of the obligations of this Limited Warranty is
authorized.
FCC Notice: This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy, and if not installed and used in accordance with the instructions
may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following
measures:
1) Reorient or relocate the receiving antenna,
2) Increase the separation between the equipment and receiver,
3) Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
4) Consult the dealer or an experienced radio/television technician for help.
Changes or modifications to this equipment not expressly approved by Honeywell
may void the user’s authority to operate this equipment.
165 Eileen Way, Syosset, New York 11791
Copyright © 2004 Honeywell International Inc.
ÊK5942V2\Š
K5942V2
7/04
|